IMPINGEMENT COOLING IN A SIMULATED DATA CENTER SERVERS WITH AN ARRAY OF ELLIPTIC AIR JETS

Loading...
Thumbnail Image

Date

Journal Title

Journal ISSN

Volume Title

Publisher

DOI

Abstract

Reducing the electricity consumption from the cooling systems in a data center can cut the energy cost. The development of the high efficiency cooling schemes can effectively save more energy from the computer room air conditioning (CRAC) system. Impingement cooling with air jets can achieve high heat transfer rates and could be used to cool local hot spots in the cabinets. A 5 x 5 jet array was designed utilizing circular and elliptic holes. The cross sectional area of the test region was 250 mm x 25 mm. The jet Reynolds numbers is 3300. Heat transfer coefficients on the target surface were investigated. Results indicated that the impingement cooling provided lower surface temperature than the traditional fan cooling.