摘要
This study investigates how high-pressure water-mist system discharge methodologies influence the fire extinction performance for pan pool fires and the corresponding mechanisms of restraining fire. The fire source is a pool-fire burner. Fine water spray is injected using a portable device. The additive in the water-mist is neither toxic nor corrosive. All the tests are regarded as fuel controlled. The fire test parameters are fuel type, nozzle discharge angle, and additive solution volume. The fuels used are heptane, gasoline, and diesel. Nozzle discharge angles are 30, 45, and 60 degrees with respect to the ground. Additive solution volumes are 0% (pure water), 3, 6, and 10%. Test results indicate that the nozzle discharge angle and additive solution volume in a water-mist fire extinction system play a significant role. Fire extinguishing efficiency is influenced by mist effects and the additive. Furthermore, the water-mist system can reduce radiation and can provide good protection for operators using portable fire extinguishing equipment. Copyright (C) 2008 John Wiley & Sons, Ltd.
所屬典藏
期刊論文引用此條目
Chang, W.-Y., Fu, P.-K., Chen, C.-H., & Shu, Y.-L. (2008). Evaluating the performance of a portable water-mist fire extinguishing system with additives. FIRE AND MATERIALS, 32(7), 383–397. https://doi.org/10.1002/fam.967