Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration
顯示簡易詮釋資料 統計資料| 欄位 | 內容 | 語言 |
|---|---|---|
dc.citation.epage |
2240 | en_US |
dc.citation.issue |
9-10 | en_US |
dc.citation.spage |
2234 | en_US |
dc.citation.volume |
54 | en_US |
dc.citation.woscount |
9 | |
dc.contributor.author |
Pongsoi, Parinya | en_US |
dc.contributor.author |
Pikulkajorn, Santi | en_US |
dc.contributor.author |
Wang, Chi-Chuan | en_US |
dc.contributor.author |
Wongwises, Somchai | en_US |
dc.contributor.department |
機械工程學系 | zh_TW |
dc.contributor.department |
Department of Mechanical Engineering | en_US |
dc.date.accessioned |
2014-12-08T15:11:49Z | |
dc.date.available |
2014-12-08T15:11:49Z | |
dc.date.issued |
2011-04-01 | en_US |
dc.description.abstract |
This study investigates the effect of fin pitches and fin materials on the air-side performance of crimped fin-and-tube heat exchangers in the range of high Reynolds numbers (4000-13000). The test samples are made from copper and aluminium with different fin pitches (f(p) = 3.2, 4.2 and 6.2 mm). It is found that the proposed simple average effectiveness equation from the pure counter and parallel circuitry arrangement can well represent the effectiveness-NTU relationship for the current z-shape arrangement. The experimental results reveal that the fin pitch casts insignificant effect on the heat transfer characteristics (Colburn j factor). However, a detectable rise of the friction factor is seen when the fin pitch is increased to f(p) = 6.2 mm. On the other hand, the effect of fin material on the airside performance is negligible. (C) 2010 Elsevier Ltd. All rights reserved. | en_US |
dc.identifier.doi |
10.1016/j.ijheatmasstransfer.2010.12.027 | en_US |
dc.identifier.issn |
0017-9310 | en_US |
dc.identifier.journal |
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER | en_US |
dc.identifier.uri |
http://dx.doi.org/10.1016/j.ijheatmasstransfer.2010.12.027 | en_US |
dc.identifier.uri |
https://ir.lib.nycu.edu.tw/handle/11536/9069 | |
dc.identifier.wosnumber |
WOS:000289011700057 | |
dc.language.iso |
en_US | en_US |
dc.subject |
Fin | en_US |
dc.subject |
Heat transfer | en_US |
dc.subject |
Heat exchanger | en_US |
dc.subject |
Air-water | en_US |
dc.subject |
Extended surface | en_US |
dc.title |
Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration | en_US |
dc.type |
Article | en_US |
檔案
- 000289011700057.pdf (968.0 KB, Adobe PDF)
所屬典藏: 期刊論文
引用此條目
Pongsoi, P., Pikulkajorn, S., Wang, C.-C., & Wongwises, S. (2011). Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 54(9-10), 2234–2240. https://doi.org/10.1016/j.ijheatmasstransfer.2010.12.027
引用文字依 APA 第 7 版格式自動產生,使用前請再核對。