Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration
檔案
- 000289011700057.pdf (968.0 KB, Adobe PDF)
日期
2011-04-01
類型
系所
期刊名稱
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
卷期與頁次
第 54 卷第 9-10 期,頁 2234–2240
ISSN
0017-9310
語言
英文
摘要
This study investigates the effect of fin pitches and fin materials on the air-side performance of crimped fin-and-tube heat exchangers in the range of high Reynolds numbers (4000-13000). The test samples are made from copper and aluminium with different fin pitches (f(p) = 3.2, 4.2 and 6.2 mm). It is found that the proposed simple average effectiveness equation from the pure counter and parallel circuitry arrangement can well represent the effectiveness-NTU relationship for the current z-shape arrangement. The experimental results reveal that the fin pitch casts insignificant effect on the heat transfer characteristics (Colburn j factor). However, a detectable rise of the friction factor is seen when the fin pitch is increased to f(p) = 6.2 mm. On the other hand, the effect of fin material on the airside performance is negligible. (C) 2010 Elsevier Ltd. All rights reserved.
網址
所屬典藏
期刊論文引用此條目
Pongsoi, P., Pikulkajorn, S., Wang, C.-C., & Wongwises, S. (2011). Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 54(9-10), 2234–2240. https://doi.org/10.1016/j.ijheatmasstransfer.2010.12.027
引用文字依 APA 第 7 版格式自動產生,使用前請再核對。
分享