标题: 钢梁接圆形钢管混凝土柱接头耐震行为
Seismic Behavior of Steel Beam to Concrete-Filled Circular Steel Tube Column Connections
作者: 罗胜宏
Sheng-Hung Lo
陈诚直
Cheng-Chih Chen
土木工程学系
关键字: 梁柱接头;实尺寸试验;夹型钢板;钢管混凝土柱;beam-to-column;full-scale test;clamping plate;concrete-filled tube column
公开日期: 2001
摘要: 钢管混凝土具有高强度、高劲度与韧性佳之优点,但其梁柱接头细节不易设计,往往需要大量焊接方能达到设计要求。因此本研究设计一夹型板式接头,其夹型钢板贯穿钢管并以开槽焊与钢管接合,夹型钢板延伸出柱面段则与钢梁填角焊接合。藉由夹型钢板贯穿钢管将梁翼应力传导入交会区,避免梁柱交接面应力集中;夹型钢板自柱面延长段补强梁翼断面,并于延长段末端形成塑铰消散地震能量。
本文进行四组实尺寸梁柱接头试验,其中两组试体设计为强柱弱梁,预期非弹性变形集中于夹型板末端塑铰处,另两组试体设计为低交会区剪力强度,预期非弹性变形集中于夹型板末端塑铰处与梁柱交会区。实验结果显示夹型板式接头可有效传递梁翼作用力至交会区。本研究采用软化压杆理论与混凝土围束效应所提出交会区剪力强度预测理论,可有效预测夹型板式梁柱接头交会区剪力强度。
Concrete-filled tube (CFT) columns possess several structural advantages such as stiffness, strength, and ductility. However, it is difficult to joint the steel beam to the circular CFT column due to its complexity. This research proposed a connection detail, which is by penetrating a pair of clamping plates through the tube and welding to the steel beam. The force-transferred mechanism of the connection is established by transferring the beam flange forces into the tube and concrete core through those clamping plates.
Four large-scale specimens were designed and fabricated to identify the possible failure mode. Test results indicate that the penetrated clamping plate connections possess the satisfactory connection strength and inelastic deformation ability required for the moment connection when the shear strength in the joint is adequately designed. Joint shear failure, presented by the shear cracking on the concrete inside the tube, is the controlled mode of failure for the flange plate connection with weak joint shear strength. The clamping plates are effective to transfer the beam flange forces into the concrete core. Proposed softened strut-and-tie model can predict the joint shear strength well.
URI: http://140.113.39.130/cdrfb3/record/nctu/#NT900015077
http://hdl.handle.net/11536/68118
显示于类别:Thesis