A numerical investigation of the geometric effects on the performance of plate finned-tube heat exchanger
檔案
- 000287071000009.pdf (743.6 KB, Adobe PDF)
日期
2011-03-01
類型
系所
期刊名稱
ENERGY CONVERSION AND MANAGEMENT
卷期與頁次
第 52 卷第 3 期,頁 1638–1643
ISSN
0196-8904
語言
英文
摘要
This study numerically examines the geometric parameters on the performance of a two-row fin-and-tube heat exchanger. Effects of fin pitch, tube pitch, fin thickness, and tube diameter are termed with. The simulation indicates that the performance, in terms of Q/Delta P and COP, increases with longitudinal tube pitch or with transverse tube pitch, and it decreases with larger tube diameter or fin thickness. An optimum value for Q/Delta P occurs at a 6-8 fpi at a fixed flow rate condition. There is not much difference in choosing the index of Q/Delta P or COP under fixed flow rate condition. However, when the simulation are performed with the actual axial fan whose P-Q curve being implemented. It is found that Q/Delta P peaks at 12 fpi while COP peaks at 16 fpi. (C) 2010 Elsevier Ltd. All rights reserved.
所屬典藏
期刊論文引用此條目
Lu, C.-W., Huang, J.-M., Nien, W. C., & Wang, C.-C. (2011). A numerical investigation of the geometric effects on the performance of plate finned-tube heat exchanger. ENERGY CONVERSION AND MANAGEMENT, 52(3), 1638–1643. https://doi.org/10.1016/j.enconman.2010.10.026