On cold-aisle containment of a container datacenter

檔案

本條目沒有附加檔案。

至出版者網站查看(DOI) ›

日期

2017-02-05

期刊名稱

APPLIED THERMAL ENGINEERING

卷期與頁次

第 112 卷,頁 133–142

ISSN

1359-4311

語言

英文

摘要

In this study, influences of various blockage arrangements as well as cold-aisle containment on the overall efficiency of a container datacenter are reported. The test container datacenter contains ten racks and the cold air is supplied from drop ceiling. The experiments are performed with each rack equally delivering a power of 3 kW. Eight different layouts are examined. Appreciable hot air recirculation prevails especially at the entrance of cold aisle. Adding blockage plates to the computer room air handler (CRAH) at the entrance of computer racks only improve marginally the associated rack cooling index (RCI). Layout with enclosing the end of cold aisle while let open the entrance of cold aisle also performs poorly. Full containment of the cold aisle with high jet air flowrate from the supplied grilles gives the worst performance. Layout with enclosing at the entrance of cold aisle but let open the end of cold aisle shows a much superior temperature distribution and a rather high RCI of 99%. Higher supplied flow may induce jet airflow pattern, causing the Coanda effect to result in fluctuating behaviors of RCI and SHI alongside the cold aisle (zigzag phenomenon). A lower supplied air flowrate without Coanda effect for a full containment design give the best overall performance. (C) 2016 Elsevier Ltd. All rights reserved.

所屬典藏

期刊論文
顯示完整詮釋資料 統計資料

引用此條目

Wang, C.-H., Tsui, Y.-Y., & Wang, C.-C. (2017). On cold-aisle containment of a container datacenter. APPLIED THERMAL ENGINEERING, 112, 133–142. https://doi.org/10.1016/j.applthermaleng.2016.10.089

BibTeX RIS

引用文字依 APA 第 7 版格式自動產生,使用前請再核對。

分享

永久網址:https://ir.lib.nycu.edu.tw/handle/11536/133168