dc.contributor.authorHung, Kuo-Shuen_US
dc.contributor.authorChung, Jenn-Chyien_US
dc.contributor.authorLiu, Chung-Cheen_US
dc.contributor.authorLin, Jun-Jieen_US
dc.contributor.authorWang, Chi-Chuanen_US
dc.date.accessioned2019-09-02T07:46:16Z-
dc.date.available2019-09-02T07:46:16Z-
dc.date.issued2019-07-01en_US
dc.identifier.issn1996-1073en_US
dc.identifier.urihttp://dx.doi.org/10.3390/en12132548en_US
dc.identifier.urihttp://hdl.handle.net/11536/152664-
dc.description.abstractA comparative study regarding the performance of real-scale oil-free centrifugal chillers having the flooded evaporator or falling film evaporator was conducted in this study. The nominal capacity for the test chillers was around 200 similar to 230 USRT (US refrigeration ton) (703 similar to 809 kW). The compressors of the two chillers were identical and R-134a was used as the working fluid. Both evaporators employed the same enhanced tubes (GEWA-B) to fulfill phase change. Tests were conducted in full, 75%, 50%, and 25% loading. Test results indicate that both chillers contained a comparable system performance with an integrated part-load value of around 8.62 similar to 8.63. The overall heat transfer coefficient for the flooded evaporator was appreciably higher (20 similar to 40%) than the falling film evaporator. This is because the falling film flowrate was below the threshold value and the heat transfer was dominated by evaporation mode. Yet, the heat transfer performance for the falling film evaporator was further jeopardized due to starvation of the film flowrate (partial dry-out), especially in the middle or bottom of the tube bundle. This phenomenon became even more pronounced at partial loading (25%), whereas the flooded evaporator did not reveal such a performance dip at partial loading.en_US
dc.language.isoen_USen_US
dc.subjectoil-free centrifugal chilleren_US
dc.subjectflooded evaporatoren_US
dc.subjectfalling film evaporatoren_US
dc.subjectheat transferen_US
dc.titleA Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator-A Case Studyen_US
dc.typeArticleen_US
dc.identifier.doi10.3390/en12132548en_US
dc.identifier.journalENERGIESen_US
dc.citation.volume12en_US
dc.citation.issue13en_US
dc.citation.spage0en_US
dc.citation.epage0en_US
dc.contributor.department機械工程學系zh_TW
dc.contributor.departmentDepartment of Mechanical Engineeringen_US
dc.identifier.wosnumberWOS:000477034700089en_US
dc.citation.woscount0en_US
顯示於類別:期刊論文