dc.description.abstract | This study explores the floor micro-vibrations induced by the automated guided vehicles (AGVs) in liquid-crystal-display (LCD) factories. The relationships between moving loads and both the vehicle weights and speeds were constructed by a modified Kanai-Tajimi (MKT) power spectral density (PSD) function whose best-fitting parameters were obtained through a regression analysis by using experimental acceleration responses of a small-scale three-span continuous beam model obtained in the laboratory. The AGV induced floor micro-vibrations under various AGV weights and speeds were then assessed by the proposed regressional MKT model. Simulation results indicate that the maximum floor micro-vibrations of the target LCD factory fall within the VC-B and VC-C levels when AGV moves at a lower speed of 1.0 m/s, while they may exceed the acceptable VC-B level when AGV moves at a higher speed of 1.5 m/s. The simulated floor micro-vibration levels are comparable to those of typical LCD factories induced by AGVs moving normally at a speed between 1.0 m/s and 2.0 m/s. Therefore, the numerical algorithm that integrates a simplified sub-structural multi-span continuous beam model and a proposed regressional MKT moving force model can provide a satisfactory prediction of AGV-induced floor micro-vibrations in LCD factories, if proper parameters of the MKT moving force model are adopted. | en_US |
dc.language.iso | en_US | en_US |
dc.subject | micro-vibration | en_US |
dc.subject | automated guided vehicle (AGV) | en_US |
dc.subject | liquid-crystal-display (LCD) | en_US |
dc.subject | moving loads | en_US |
dc.subject | modified Kanai-Tajimi model | en_US |
dc.subject | power spectral density (PSD) | en_US |
dc.title | AGV-induced floor micro-vibration assessment in LCD factories by using a regressional modified Kanai-Tajimi moving force model | en_US |
dc.type | Article | en_US |
dc.identifier.journal | STRUCTURAL ENGINEERING AND MECHANICS | en_US |
dc.citation.volume | 45 | en_US |
dc.citation.issue | 4 | en_US |
dc.citation.spage | 543 | en_US |
dc.citation.epage | 568 | en_US |
dc.contributor.department | 土木工程學系 | zh_TW |
dc.contributor.department | Department of Civil Engineering | en_US |
dc.identifier.wosnumber | WOS:000325329600007 | - |
dc.citation.woscount | 0 | - |