標題: | Performance evaluation of a tube-in-tube CO2 gas cooler used in a heat pump water heater |
作者: | Yu, Pei-Yu Lin, Wei-Keng Wang, Chi-Chuan 機械工程學系 Department of Mechanical Engineering |
關鍵字: | Carbon dioxide;Supercritical;Gas cooler;Tube-in-tube heat exchanger |
公開日期: | 1-四月-2014 |
摘要: | In this study, investigation of the performance of a tube-in-tube counter-flow water-cooled CO2 gas cooler operating above and near critical pressure is presented using a heat pump water heater with CO2 flowing in the annulus side. A tube-in-tube heat exchanger model applicable for supercritical fluid CO2 and water was also developed and validated. The measured total heat transfer capacity ranged from 1.31 to 4.06 kW at various test conditions. The calculations show good agreement with the experimental results. The results demonstrate that the variation of CO2 temperature tends to show very slow decreasing near the pseudo-critical region when compared to the inlet region. Yet this phenomenon becomes more pronounced as the inlet pressure is close to the critical pressure (73.8 bar). The calculation also reveals a peculiar phenomenon that the local heat transfer rate of the heat exchanger peaks within the heat exchanger near the pseudo critical region due to the drastic rise of specific heat (C-p value). (C) 2014 Elsevier Inc. All rights reserved. |
URI: | http://dx.doi.org/10.1016/j.expthermflusci.2014.01.007 http://hdl.handle.net/11536/24274 |
ISSN: | 0894-1777 |
DOI: | 10.1016/j.expthermflusci.2014.01.007 |
期刊: | EXPERIMENTAL THERMAL AND FLUID SCIENCE |
Volume: | 54 |
Issue: | |
起始頁: | 304 |
結束頁: | 312 |