标题: 水平双套管中冷媒流量或热通量振荡引起之冷媒R-134a周期性流动沸腾研究
Time Periodic Flow Boiling Heat Transfer and Associated Bubble Characteristics of Refrigerant R-134a in a Horizontal Annular Duct due to Flow Rate or Heat Flux Oscillation
作者: 陈建安
Chen, Chien-An
林清发
Lin, Tsing-Fa
机械工程学系
关键字: 周期性流动沸腾;周期性蒸发热传;冷媒R-134a;气泡特征;流量振荡;热通量振荡;Time periodic flow boiling;Time periodic evaporation;R-134a;Bubble characteristics;Flow rate oscillation;Heat flux oscillation
公开日期: 2009
摘要: 本研究以实验方式探讨冷媒流量或热通量周期性振荡对流动沸腾热传(含饱和、次冷流动沸腾及蒸发热传)及相关气泡特征和蒸发流谱之影响。以环保冷媒R-134a为工作流体流入一水平狭窄双套管之测试段,并流道之间隙由1.0至5.0mm。测试段则由玻璃外管及加热内铜管组成来量测热传系数及流场观测。一电桥式加热棒置于铜管内部提供热通量加热狭窄流道内流动之冷媒。
首先第一部分,提出冷媒R-134a在冷媒流量周期性振荡对饱和、次冷流动沸腾及蒸发热传之测试结果。从所量测之实验结果发现,当所施加之热通量接近稳态流动沸腾成核所需的起始热通量时,会有间歇性流动沸腾现象产生。而在次冷流动沸腾下,间歇性流动沸腾现象会发生的实验参数范围则是更小。随着增加所施加之热通量,则会由间歇性流动沸腾现象转换成持续流动沸腾现象。此外,冷媒流量周期性振荡对经由时间平均的沸腾曲线及热传系数几乎没有影响。并且,壁温、气泡特征和蒸发流谱会随着冷媒流量周期性振荡,而有相同频率的震荡。再者,在持续流动沸腾下长周期或大振幅时会导致壁温、气泡特征振荡更为强烈。从流场观测之结果显示在第一个半周期时气泡脱离尺寸随着质通量减小而增加、气泡脱离频率随着质通量减小而减小,但是气泡成核址密度则随着质通量减小而增加,在第二个半周期时则有相反趋势。冷媒流量周期性振荡时气泡脱离尺寸和气泡成核址密度比气泡脱离频率更占有主导影响因素,所以会造成随着质通量减小而壁温下降、热传系数上升与单相强制对流时相反的趋势。但是,振荡周期对于气泡特征的影响是不明显的。除此之外,在中间干度时经由冷媒流量周期振荡,则会造成蒸发流谱由成核沸腾主导转换成液膜所主导呈周期性改变。最后,我们把这个实验中间歇性流动沸腾现象所占有的实验参数范围资料作分析,求出间歇性流动沸腾之边界经验式。
接着第二部分,提出冷媒R-134a在热通量周期性振荡对饱和、次冷流动沸腾及蒸发热传之测试结果。从所量测之实验结果发现,当所施加之平均热通量接近稳态流动沸腾成核所需的起始热通量时,会有间歇性流动沸腾现象产生。而在次冷流动沸腾下,间歇性流动沸腾现象会发生的实验参数范围则是更小。随着增加所施加之平均热通量,则会由间歇性流动沸腾现象转换成持续流动沸腾现象。此外,热通量周期性振荡对经由时间平均的沸腾曲线及热传系数几乎没有影响。并且,壁温、气泡特征和蒸发流谱会随着热通量周期性振荡,而有相同频率的震荡。再者,在持续流动沸腾下长周期或大振幅时会导致壁温、气泡特征振荡更为强烈。从流场观测之结果显示在第一个半周期时气泡脱离尺寸随着热通量减小而减小、气泡脱离频率随着热通量减小而减小、气泡成核址密度随着热通量减小而减小,在第二个半周期时则有相反趋势。除此之外,在中间干度时经由热通量周期振荡,则会造成蒸发流谱由成核沸腾主导转换成液膜所主导周期性改变。最后,我们把这个实验间歇性流动沸腾现象所占有的实验参数范围资料作分析,求出间歇性流动沸腾之边界经验式。
Experiments have been conducted here to investigate how the imposed time periodic refrigerant flow rate or heat flux oscillation affects the saturated and subcooled flow boiling heat transfer and associated bubble characteristics for refrigerant R-134a in a horizontal narrow annular duct. Besides, the evaporation heat transfer of R-134a flow in the same duct are examined. The test section for the horizontal annular duct consists of an outer pipe made of Pyrex glass and an inner heated copper pipe, intending to measure the boiling heat transfer coefficient and to facilitate the visualization of boiling processes. A cartridge heater is installed inside the inner pipe to provide the required heat flux to the refrigerant flow in the narrow annular duct. In the study the gap of the duct is varied from 1.0 to 5.0 mm with the mean refrigerant mass flux, saturated temperature, imposed heat flux and mean vapor quality respectively ranging from 100 to 600 kg/m2s, 5 to 15℃, 0 to 45 kW/m2 and 0.05 to 0.95. The inlet subcooling is varied from 3 to 6℃. In particular, attention is focused on the time periodic flow boiling characteristics affected by the mean levels, amplitudes and periods of the flow rate or heat flux oscillation.
Some results have been obtained and are reported here. In the first part of the present study, experiments have been carried out to investigate the effects of the imposed time periodic refrigerant flow rate oscillation in the form of nearly a triangular wave on the saturated and subcooled flow boiling and evaporation heat transfer and associated bubble characteristics of R-134a in a horizontal narrow annular duct. The results indicate that when the imposed heat flux is close to that for the onset of stable flow boiling, intermittent flow boiling appears in which nucleate boiling on the heated surface only exists in a partial time interval of each periodic cycle. But the intermittent boiling prevails in narrower ranges of the experimental parameters in the subcooled flow boiling. At somewhat higher heat flux persistent boiling prevails. Besides, the refrigerant flow rate oscillation is found to negligibly affect the time-average boiling curves and heat transfer coefficients. Moreover, the heated wall temperature, bubble departure diameter and frequency, active nucleation site density, and evaporating flow pattern are noted to oscillate periodically in time as well and at the same frequency as the imposed mass flux oscillation. Furthermore, in the persistent boiling the resulting Tw oscillation is stronger for a longer period and a larger amplitude of the mass flux oscillation. And for a larger amplitude of the mass flux oscillation, stronger temporal oscillations in dp, f and nac are noted. Specifically, in the first half of the periodic cycle in which the mass flux decreases with time the departing bubbles are larger and the departure rate is lower but the active nucleation site density is higher. The opposite is the case in the second half of the cycle in which the mass flux increases. The effects of the mass flux oscillation on the departing bubble size and active nucleation site density dominate over the bubble departure frequency, causing the heated wall temperature to decrease and heat transfer coefficient to increase at reducing G in the flow boiling, opposing to that in the single-phase flow. But the bubble characteristics are only mildly affected by the period of the mass flux oscillation. However, a short time lag in the Tw oscillation is also noted. Finally, flow regime maps are provided to delineate the boundaries separating different boiling regimes for the R-134a saturated and subcooled flow boiling in the annular duct.
Moreover, at the intermediate vapor quality changes in the evaporating flow patterns between that dominated by the nucleation bubbles and liquid film resulting from the refrigerant flow rate oscillation take place cyclically. Furthermore, after the time lag the heated pipe wall temperature decreases and the evaporation heat transfer gets better as the mass flux decreases in the first half of the periodic cycle. In the second half of the cycle in which the mass flux increases the opposite processes occur. These unusual changes of the heating surface temperature and heat transfer coefficient with the mass flux oscillation are attributed to the strong effects of the mass flux oscillation on the state of the refrigerant at the duct inlet and hence on the changes of the vapor quality and liquid film thickness in the evaporating flow.
In the second part of the present study, experiments are conducted to investigate how the imposed time periodic heat flux oscillation also in the form of nearly a triangular wave on the refrigerant R-134a saturated and subcooled flow boiling and evaporation heat transfer and associated bubble characteristics in a horizontal narrow annular duct. The results also show that when the mean imposed heat flux is close to that for the onset of stable flow boiling, intermittent flow boiling appears in which nucleate boiling on the heated surface only exists in a partial interval of each periodic cycle. But the intermittent boiling appears in narrower ranges of experimental parameters in the subcooled flow boiling. At somewhat higher heat flux persistent boiling prevails. Besides, the heat flux oscillation does not noticeably affect the time-average boiling curves and heat transfer coefficients. Moreover, the heated wall temperature, bubble departure diameter and frequency, active nucleation site density, and evaporating flow pattern are found to oscillate periodically in time as well and at the same frequency as the imposed heat flux oscillation. Furthermore, in the persistent boiling the resulting oscillation amplitudes of the heated surface temperature, heat transfer coefficient and bubble parameters, such as dp, f and nac, get larger for a longer period and a larger amplitude of the imposed heat flux oscillation and for a higher mean imposed heat flux. A significant time lag in the Tw oscillation is noted. In the first half of the periodic cycle in which the heat flux decreases with time, after the time lag the heated wall temperature decreases with time, so does the bubble parameters. The opposite processes occur in the second half of the cycle in which q increases with time. Finally, flow regime maps are provided to delineate the boundaries separating different boiling regimes for the R-134a saturated and subcooled flow boiling in the annular duct.
Moreover, at the intermediate vapor quality changes in the evaporating flow patterns between that dominated by the nucleation bubbles and by the liquid film resulting from the heat flux oscillation take place cyclically. Furthermore, after the time lag the heated pipe wall temperature decreases and the evaporation heat transfer gets worse as the heat flux decreases in the first half of the periodic cycle. In the second half of the cycle in which the heat flux increases the opposite processes occur. These changes of the heating surface temperature and heat transfer coefficient with the heat flux oscillation are attributed to the strong effects of the heat flux oscillation on the changes of the vapor quality and liquid film thickness in the evaporating flow.
URI: http://140.113.39.130/cdrfb3/record/nctu/#GT079514816
http://hdl.handle.net/11536/41127
显示于类别:Thesis