<link rel="stylesheet" href="styles.cf390c6bfbe7555f.css"> Skip to main content

Film condensation of HCFC-22 on horizontal enhanced tubes

Loading...
Thumbnail Image

Journal Title

Journal ISSN

Volume Title

Publisher

DOI

10.1016/0735-1933(95)00086-0

Abstract

Experiments were conducted to study the condensation heat transfer characteristics of horizontal enhanced tubes. In the current experiment, six different enhanced tubes, including 26, 40 fpi low fin tubes and four three-dimensional-fin tubes, were tested. The working fluid used in the experiment was HCFC-22. Data were presented in the form of overall heat transfer coefficient at three working pressures, namely 1.32, 1.47 and 1.62 Mpa. In addition, the condensing heat transfer coefficients for the test tubes were obtained from the Wilson plot technique.