標題: | Analysis of evaporation of non-azeotropic refrigerants in a horizontal tube |
作者: | Chiou, CB Lu, DC Wang, CC 機械工程學系 Department of Mechanical Engineering |
關鍵字: | non-azeotropic refrigerants;evaporation;model |
公開日期: | 1-十月-1996 |
摘要: | Based on the two-phase separated model, a detailed one-dimensional model for binary mixtures had been proposed to study the in-tube evaporation in a horizontal tube. The present model can predict the detailed variation of the composition, temperature, heat transfer rate and pressure drop of various binary mixtures under constant heat flux, counter-flow, or parallel-flow conditions. The predicted results agree favorably with the Takamatsu et al. [Int. J. Neat Mass Transfer 36, 3555-3563 (1993)] and Jung et al. [Exp. Heat Transfer 2, 237-255 (1989)] experimental data. Also, it is found that the full evaporation of the non-azeotropic refrigerants may require a corresponding temperature higher than the saturation temperature of the less volatile component. The non-linear variation of the property plays an important role in the heat transfer and pressure drop characteristics of the refrigerant mixtures. Copyright (C) 1996 Elsevier Science Ltd. |
URI: | http://dx.doi.org/10.1016/1359-4311(95)00089-5 http://hdl.handle.net/11536/1011 |
ISSN: | 1359-4311 |
DOI: | 10.1016/1359-4311(95)00089-5 |
期刊: | APPLIED THERMAL ENGINEERING |
Volume: | 16 |
Issue: | 10 |
起始頁: | 817 |
結束頁: | 827 |
顯示於類別: | 期刊論文 |