摘要: Based on the two-phase separated model, a detailed one-dimensional model for binary mixtures had been proposed to study the in-tube evaporation in a horizontal tube. The present model can predict the detailed variation of the composition, temperature, heat transfer rate and pressure drop of various binary mixtures under constant heat flux, counter-flow, or parallel-flow conditions. The predicted results agree favorably with the Takamatsu et al. [Int. J. Neat Mass Transfer 36, 3555-3563 (1993)] and Jung et al. [Exp. Heat Transfer 2, 237-255 (1989)] experimental data. Also, it is found that the full evaporation of the non-azeotropic refrigerants may require a corresponding temperature higher than the saturation temperature of the less volatile component. The non-linear variation of the property plays an important role in the heat transfer and pressure drop characteristics of the refrigerant mixtures. Copyright (C) 1996 Elsevier Science Ltd.
URI: http://dx.doi.org/10.1016/1359-4311(95)00089-5
http://hdl.handle.net/11536/1011
ISSN: 1359-4311
DOI: 10.1016/1359-4311(95)00089-5
期刊: APPLIED THERMAL ENGINEERING
Volume: 16
Issue: 10
起始頁: 817
結束頁: 827