標題: | Active noise cancellation in ducts using internal model-based control algorithms |
作者: | Hu, JS 交大名義發表 電控工程研究所 National Chiao Tung University Institute of Electrical and Control Engineering |
公開日期: | 1-三月-1996 |
摘要: | A feedback control algorithm based on the internal model principle is proposed to solve the active noise control (ANC) problem in ducts. Because of its infinite open-loop gain at selected frequencies, the controller is able, at the cancellation speaker position, to block noise transmission of these frequencies. In other words, the speaker acts like a totally reflective boundary, Stability analysis of the closed-loop system is performed using the Nyquist criterion, Experimental results confirm the theoretical analysis, showing an average noise level reduction of 30 to 40 dB at the target frequencies. |
URI: | http://dx.doi.org/10.1109/87.486342 http://hdl.handle.net/11536/1425 |
ISSN: | 1063-6536 |
DOI: | 10.1109/87.486342 |
期刊: | IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY |
Volume: | 4 |
Issue: | 2 |
起始頁: | 163 |
結束頁: | 170 |
顯示於類別: | 期刊論文 |