標題: Active noise cancellation in ducts using internal model-based control algorithms
作者: Hu, JS
交大名義發表
電控工程研究所
National Chiao Tung University
Institute of Electrical and Control Engineering
公開日期: 1-三月-1996
摘要: A feedback control algorithm based on the internal model principle is proposed to solve the active noise control (ANC) problem in ducts. Because of its infinite open-loop gain at selected frequencies, the controller is able, at the cancellation speaker position, to block noise transmission of these frequencies. In other words, the speaker acts like a totally reflective boundary, Stability analysis of the closed-loop system is performed using the Nyquist criterion, Experimental results confirm the theoretical analysis, showing an average noise level reduction of 30 to 40 dB at the target frequencies.
URI: http://dx.doi.org/10.1109/87.486342
http://hdl.handle.net/11536/1425
ISSN: 1063-6536
DOI: 10.1109/87.486342
期刊: IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY
Volume: 4
Issue: 2
起始頁: 163
結束頁: 170