dc.description.abstractEffect of airflow managements on the efficiency index of a small container data center having overhead air supply is reported in this study. Seventeen arrangements and configurations regarding the airflow and blockage arrangements are experimentally examined and compared. Test results indicate an appreciable hot air recirculation occurring for rack arrangement without any blockage, and the hot spot occurs at the second rack alongside the cold aisle. The hot spot had moved to the first rack when the blockage plate is installed on the rack top. Rack locations relative to air handler casts a negligible effect on the efficiency index, and it is comparatively more effective by sealing the trailing of the cold aisle. A smaller cold-aisle spacing helps to lower the temperature distribution, and an additional opening of the supplied vent will not help in removal of hot spot. Shutting off the grille in the center of cold aisle is also unable to fix the hot air recirculation and may even incur hot air reversal. The hot air reversal can be removed by adding additional blockage plate at the flow reversal section. Higher supplied air flow rate also improves the efficiency index considerably.en_US
dc.language.isoen_USen_US
dc.subjectdata centeren_US
dc.subjectoverheaden_US
dc.subjectcontaineren_US
dc.subjectairflow managementen_US
dc.subjectrack cooling indexen_US
dc.subjectsupplied heat indexen_US
dc.titleAirflow Management on the Efficiency Index of a Container Data Center Having Overhead Air Supplyen_US
dc.typeArticleen_US
dc.identifier.doi10.1115/1.4038114en_US
dc.identifier.journalJOURNAL OF ELECTRONIC PACKAGINGen_US
dc.citation.volume139en_US
dc.contributor.department機械工程學系zh_TW
dc.contributor.departmentDepartment of Mechanical Engineeringen_US
dc.identifier.wosnumberWOS:000414437700008en_US
Appears in Collections:Articles