標題: The Effect of Ventilation Types on Pollutant Removal in a Large Space Plant with Multiple Pollutant Sources
作者: Huang, Jeng-Ming
Hsu, Shou-Ping
Wu, Yu-Lieh
Chen, Hung-Yuen
Wang, Chi-Chuan
機械工程學系
Department of Mechanical Engineering
關鍵字: Large space;Multiple pollutant sources;CFD;General displacement;Local exhaust
公開日期: 1-Oct-2011
摘要: This study numerically investigated the influences of ventilation designs on pollutant removal in a large space with multiple pollutant sources. The types of ventilation include general displacement and local exhaust ventilation with either partitioned or non-partitioned working field. The study demonstrated that the outlet positions and outlet flow rate distribution for local exhaust ventilation are more important than those of the general displacement type. It would be more effective to design local exhaust by placing the outlets on the midstream and downstream of the machines rather than on all the machines. The results also demonstrated that the effect of local exhaust type would not be more superior to the general displacement type due to the large space in plant and multiple pollutant sources such as oil gas pollutant source, mist of metalworking fluid, etc.
URI: http://dx.doi.org/10.1177/1420326X11406606
http://hdl.handle.net/11536/14758
ISSN: 1420-326X
DOI: 10.1177/1420326X11406606
期刊: INDOOR AND BUILT ENVIRONMENT
Volume: 20
Issue: 5
起始頁: 488
結束頁: 500
Appears in Collections:Articles


Files in This Item:

  1. 000296749400002.pdf

If it is a zip file, please download the file and unzip it, then open index.html in a browser to view the full text content.