Simulation and testing of pollutant dispersion during preventive maintenance in a cleanroom
檔案
- 000269276900001.pdf (596.3 KB, Adobe PDF)
日期
2009-12-01
類型
系所
期刊名稱
BUILDING AND ENVIRONMENT
卷期與頁次
第 44 卷第 12 期,頁 2319–2326
ISSN
0360-1323
語言
英文
摘要
Sulfur hexafluoride (SF(6)) of >99.9% purity was artificially released to simulate the emission sources in the etching-thin film area of a working cleanroom in a semiconductor fab at the rate of 492 g/h. Three mobile Fourier transform infrared spectrometers (FTIRs, detection limit: 10 ppb) were used simultaneously to measure the real time SF6 concentrations at different locations of the cleanroom. A three-dimensional numerical model was also used to predict the unsteady gas concentration distribution and the results were compared with the experimental data. Due to high dilution of the pollutant in the cleanroom, it is found that the current gas sensors may not be sensitive enough and a better monitoring system and strategy is needed to protect workers from injury and to ensure good product yield. After comparison with the validated numerical results. the well-mixed model is found to predict the peak pollutant concentrations within a reasonable range which is 0.34-1.33 times the experimental values except when the monitored distance is very close to the release point. The well-mixed model is shown to be capable of predicting a reasonable attainable maximum concentration once a pollutant leaks in the cleanroom. (C) 2009 Elsevier Ltd. All rights reserved.
所屬典藏
期刊論文引用此條目
Shih, H.-Y., Huang, S.-H., Li, S.-N., Chen, S.-C., & Tsai, C.-J. (2009). Simulation and testing of pollutant dispersion during preventive maintenance in a cleanroom. BUILDING AND ENVIRONMENT, 44(12), 2319–2326. https://doi.org/10.1016/j.buildenv.2009.03.018
引用文字依 APA 第 7 版格式自動產生,使用前請再核對。
分享
永久網址:https://ir.lib.nycu.edu.tw/handle/11536/6348