標題: | The Flow Analysis and Performance Improvement of the Flow Return System in High Pressure Fans |
作者: | Yen, Hung-Cheng Cheng, Yung Jen Huang, Jeng-Min Lu, Chi-Wen Tsai, Yeah-Hann 機械工程學系 Department of Mechanical Engineering |
關鍵字: | High pressure fan;flow return system;drag coefficients;performance improvement;CFD |
公開日期: | 1-十二月-2012 |
摘要: | This study numerically investigated the flow return system performances of two-stage high pressure fans. The parameters include inflow angle, length, exit width of vaneless diffuser and the blade number of deswirl vane. This study used the tested impeller to verify the accuracy of numerical calculations, with good consistency. The analytic results showed that the overall pressure loss of impeller and flow return system is effectively reduced when the inflow angle of vaneless diffuser is 15 degrees and tangential to wheel velocity ratio is 0.46. A vaneless diffuser was required and its length referred to the maximum outer diameter of the volute casing. The performance of a contracted-wall vaneless diffuser was not improved over that of a parallel-wall one. The suggested number of blades in a deswirl vane was 12. The downstream affects the upstream in several areas inside the flow return system, thus, the flow return system must be calculated integrally. |
URI: | http://dx.doi.org/10.1515/tjj-2012-0008 http://hdl.handle.net/11536/21306 |
ISSN: | 0334-0082 |
DOI: | 10.1515/tjj-2012-0008 |
期刊: | INTERNATIONAL JOURNAL OF TURBO & JET-ENGINES |
Volume: | 29 |
Issue: | 4 |
起始頁: | 223 |
結束頁: | 233 |
顯示於類別: | 期刊論文 |