標題: | 垂直往復式冷卻渠道之混合對流實驗 A mixed convection experiment of a vertical cooling channel under reciprocating motion |
作者: | 林敬倫 Ching-Lun Lin 傅武雄 Wu-Shung Fu 機械工程學系 |
關鍵字: | 混合對流;mixed convection |
公開日期: | 2007 |
摘要: | 本研究主要目的在以實驗方法去探討混合對流在一振動U型渠道內對壁面熱傳效率之影響情形,並搭配數值模擬來提高實驗之可信度。實驗設備大致上可以分為三部份︰冷卻渠道、往復運動機構、溫度控制系統,工作流體為空氣。另外使用放煙線法進行流場可視化的拍攝,以實際流場變化情形與數值模擬之流線圖互相驗證,兩者結果非常吻合。
實驗針對不同的進口流體雷諾數和渠道無因次往復振動頻率及不同溫差下來進行討論,由結果得知熱傳效率會因為渠道振動而提高,熱傳增益受到進口流體雷諾數增加影響較大,相較之下渠道低無因次振動頻率增加效果較不明顯,所得到最大熱傳增益在35%以內。且溫度增加會使得自然對流效應增強,使部分加熱區熱傳效率增加。整體看來混合對流其熱傳效率較強制對流來的好。 In order to investigate the heat transfer phenomena in a U-shaped channel with reciprocating motion, an experimental work is conducted and validated by an auxiliary computational procedure simultaneously. The experimental apparatus consist of three parts, a cooling channel, reciprocating mechanism and heating control. The working fluid is air and the parameters of Reynolds number , temperature and oscillating frequency are varied. In addition, a flow visualization using the Smoke-wire method is adopted to indicate the flow field and compared with the streamline of the numerical results. The comparisons between experimental and numerical results are consistent well. The results show that the heat transfer rate is mainly dominated by Reynolds number, and less affected by increasing the low oscillating frequency. The enhancement of the heat transfer is confirmed and within 35% in this study. In general , the aid of mixed convection is to remove more heat than force convection. |
URI: | http://140.113.39.130/cdrfb3/record/nctu/#GT009514565 http://hdl.handle.net/11536/38554 |
Appears in Collections: | Thesis |
Files in This Item:
If it is a zip file, please download the file and unzip it, then open index.html in a browser to view the full text content.