標題: | Evaluating the performance of a portable water-mist fire extinguishing system with additives |
作者: | Chang, Wen-Yao Fu, Ping-Kun Chen, Chiun-Hsun Shu, Yi-Liang 機械工程學系 Department of Mechanical Engineering |
關鍵字: | water-mist;fire protection;portable;additive |
公開日期: | 1-十一月-2008 |
摘要: | This study investigates how high-pressure water-mist system discharge methodologies influence the fire extinction performance for pan pool fires and the corresponding mechanisms of restraining fire. The fire source is a pool-fire burner. Fine water spray is injected using a portable device. The additive in the water-mist is neither toxic nor corrosive. All the tests are regarded as fuel controlled. The fire test parameters are fuel type, nozzle discharge angle, and additive solution volume. The fuels used are heptane, gasoline, and diesel. Nozzle discharge angles are 30, 45, and 60 degrees with respect to the ground. Additive solution volumes are 0% (pure water), 3, 6, and 10%. Test results indicate that the nozzle discharge angle and additive solution volume in a water-mist fire extinction system play a significant role. Fire extinguishing efficiency is influenced by mist effects and the additive. Furthermore, the water-mist system can reduce radiation and can provide good protection for operators using portable fire extinguishing equipment. Copyright (C) 2008 John Wiley & Sons, Ltd. |
URI: | http://dx.doi.org/10.1002/fam.967 http://hdl.handle.net/11536/8226 |
ISSN: | 0308-0501 |
DOI: | 10.1002/fam.967 |
期刊: | FIRE AND MATERIALS |
Volume: | 32 |
Issue: | 7 |
起始頁: | 383 |
結束頁: | 397 |
顯示於類別: | 期刊論文 |