標題: A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator-A Case Study
作者: Hung, Kuo-Shu
Chung, Jenn-Chyi
Liu, Chung-Che
Lin, Jun-Jie
Wang, Chi-Chuan
機械工程學系
Department of Mechanical Engineering
關鍵字: oil-free centrifugal chiller;flooded evaporator;falling film evaporator;heat transfer
公開日期: 1-Jul-2019
摘要: A comparative study regarding the performance of real-scale oil-free centrifugal chillers having the flooded evaporator or falling film evaporator was conducted in this study. The nominal capacity for the test chillers was around 200 similar to 230 USRT (US refrigeration ton) (703 similar to 809 kW). The compressors of the two chillers were identical and R-134a was used as the working fluid. Both evaporators employed the same enhanced tubes (GEWA-B) to fulfill phase change. Tests were conducted in full, 75%, 50%, and 25% loading. Test results indicate that both chillers contained a comparable system performance with an integrated part-load value of around 8.62 similar to 8.63. The overall heat transfer coefficient for the flooded evaporator was appreciably higher (20 similar to 40%) than the falling film evaporator. This is because the falling film flowrate was below the threshold value and the heat transfer was dominated by evaporation mode. Yet, the heat transfer performance for the falling film evaporator was further jeopardized due to starvation of the film flowrate (partial dry-out), especially in the middle or bottom of the tube bundle. This phenomenon became even more pronounced at partial loading (25%), whereas the flooded evaporator did not reveal such a performance dip at partial loading.
URI: http://dx.doi.org/10.3390/en12132548
http://hdl.handle.net/11536/152664
ISSN: 1996-1073
DOI: 10.3390/en12132548
期刊: ENERGIES
Volume: 12
Issue: 13
起始頁: 0
結束頁: 0
Appears in Collections:Articles