標題: A numerical investigation of the geometric effects on the performance of plate finned-tube heat exchanger
作者: Lu, Chi-Wen
Huang, Jeng-Min
Nien, W. C.
Wang, Chi-Chuan
機械工程學系
Department of Mechanical Engineering
關鍵字: Fin-and-tube heat exchanger;Axial fan;CFD
公開日期: 1-Mar-2011
摘要: This study numerically examines the geometric parameters on the performance of a two-row fin-and-tube heat exchanger. Effects of fin pitch, tube pitch, fin thickness, and tube diameter are termed with. The simulation indicates that the performance, in terms of Q/Delta P and COP, increases with longitudinal tube pitch or with transverse tube pitch, and it decreases with larger tube diameter or fin thickness. An optimum value for Q/Delta P occurs at a 6-8 fpi at a fixed flow rate condition. There is not much difference in choosing the index of Q/Delta P or COP under fixed flow rate condition. However, when the simulation are performed with the actual axial fan whose P-Q curve being implemented. It is found that Q/Delta P peaks at 12 fpi while COP peaks at 16 fpi. (C) 2010 Elsevier Ltd. All rights reserved.
URI: http://dx.doi.org/10.1016/j.enconman.2010.10.026
http://hdl.handle.net/11536/9217
ISSN: 0196-8904
DOI: 10.1016/j.enconman.2010.10.026
期刊: ENERGY CONVERSION AND MANAGEMENT
Volume: 52
Issue: 3
起始頁: 1638
結束頁: 1643