標題: | A numerical investigation of the geometric effects on the performance of plate finned-tube heat exchanger |
作者: | Lu, Chi-Wen Huang, Jeng-Min Nien, W. C. Wang, Chi-Chuan 機械工程學系 Department of Mechanical Engineering |
關鍵字: | Fin-and-tube heat exchanger;Axial fan;CFD |
公開日期: | 1-三月-2011 |
摘要: | This study numerically examines the geometric parameters on the performance of a two-row fin-and-tube heat exchanger. Effects of fin pitch, tube pitch, fin thickness, and tube diameter are termed with. The simulation indicates that the performance, in terms of Q/Delta P and COP, increases with longitudinal tube pitch or with transverse tube pitch, and it decreases with larger tube diameter or fin thickness. An optimum value for Q/Delta P occurs at a 6-8 fpi at a fixed flow rate condition. There is not much difference in choosing the index of Q/Delta P or COP under fixed flow rate condition. However, when the simulation are performed with the actual axial fan whose P-Q curve being implemented. It is found that Q/Delta P peaks at 12 fpi while COP peaks at 16 fpi. (C) 2010 Elsevier Ltd. All rights reserved. |
URI: | http://dx.doi.org/10.1016/j.enconman.2010.10.026 http://hdl.handle.net/11536/9217 |
ISSN: | 0196-8904 |
DOI: | 10.1016/j.enconman.2010.10.026 |
期刊: | ENERGY CONVERSION AND MANAGEMENT |
Volume: | 52 |
Issue: | 3 |
起始頁: | 1638 |
結束頁: | 1643 |
顯示於類別: | 期刊論文 |